The Numbering System was release for general use in 1956 and become an industry standard.
Numbering designation and safety classification of the refrigerants is presented in ASHRAE standard 34-1989.
Method of Designating Refrigerant by number is as Follows :-
1. FIRST DIGIT ON THE RIGHT = NO. OF FLUORINE ATOMS
2. SECOND DIGIT FROM THE RIGHT = NO. OF HYDROGEN ATOMS PLUS ONE
3. THIRD DIGIT FROM THE RIGHT = NO. OF CARBON ATOMS MINUS ONE
4. FOURTH DIGIT FROM THE RIGHT = NO. OF UNSATURATED CARBON – CARBON BONDS IN THE COMPOUND.
For Example :–
R134a :-
4 = Number of Fluorine Atoms = 4
3 = Number of Hydrogen Atoms + 1 = 3
1 = Number of Carbon Atoms -1 = 1
The “a” suffix indicated that the isomer is unbalanced by one Atom.
R404A :-
4= 400 Series Denotes Zeotropic Mix
0= Chronological numbering designating the components of the mix but not the % of constituents.
4= Chronological numbering designating the components of the mix but not the % of constituents.
A= Upper case letter Denote Specific Composition.